The table ampacity is not the ampacity. Derate it.
The number in Table 310.16 assumes 86°F air and no more than three current-carrying conductors — conditions that vanish in attics, rooftops, and stuffed conduits. This calculator runs the full NEC 310.15 method: start at the conductor's insulation column, apply ambient temperature correction and bundling adjustment, then cap the result at the termination-temperature column per 110.14(C), because the weakest link governs. It also applies the 240.4(D) small-conductor breaker caps and the 125% continuous-load rule.
Electricians in hot climates use it every summer — an attic at 122°F quietly strips a third of a conductor's rating. Solar installers and EV-circuit runners use it to prove the 125% continuous-load math holds after derating, which is the first thing a plan reviewer checks.
The termination cap. NEC 110.14(C) says the circuit ampacity cannot exceed the column matching the lowest-rated termination in the circuit — usually 75°C for modern breakers. So even though 12 AWG THHN starts at 30A in the 90°C column, it can never exceed the 25A in the 75°C column after derating. You derate from the high column, then cap at the low one.
Grounds never count. Neutrals only count when they carry substantial harmonic current (nonlinear loads like VFDs and LED drivers on 3-phase systems). For a typical single-phase circuit, only the ungrounded (hot) conductors count.
A continuous load (3+ hours: lighting, HVAC, EV charging) must be multiplied by 1.25 before comparing to conductor ampacity — a 20A continuous load requires conductors rated for 25A after all derating. On a 12 AWG run at 75°C terminations, that uses the entire 25A allowance with zero margin.
Often yes: NEC 240.4(B) allows rounding to the next standard breaker size when the ampacity doesn't match one, but this calculator reports the largest breaker not exceeding your final ampacity — the conservative answer — and applies the 240.4(D) hard caps of 15/20/30A for 14/12/10 AWG copper, where rounding up is not allowed.