Size it from the table, not the nameplate.
Motor circuits break the normal wiring intuition: the breaker is deliberately oversized to survive starting inrush, and the wire is sized from NEC table current — not the motor nameplate — so the circuit stays legal when the motor is eventually swapped. This calculator runs the full Article 430 workflow: table FLC by horsepower and voltage, minimum conductor ampacity at 125%, minimum wire size on the correct termination column, maximum breaker or fuse per Table 430.52, and the 115% disconnect rating.
Electricians and maintenance techs use it when a motor gets swapped or a compressor gets added: table FLC, 125% wire, 250% breaker, 115% disconnect — the four numbers on every motor inspection tag. The nameplate-vs-table rule is the part apprentices get wrong, and the calculator makes it impossible.
Starting inrush. Motors draw 6–8× their running current for the moments it takes the rotor to spin up, so a breaker sized at the normal 125% rule would trip on every start. The oversized breaker only protects against short circuits and ground faults — the separate overload relay, set at 115–125% of nameplate amps, protects the motor while it runs.
NEC 430.6 requires the table values for conductor and breaker sizing precisely because nameplates vary — a high-efficiency replacement motor draws less than a cheap one, and the circuit must stay safe across swaps. The nameplate is reserved for the overload relay setting (430.32).
Per 110.14(C), circuits rated 100A or less use the 60°C ampacity column unless the equipment is marked for 75°C. A 5 HP 230V single-phase motor needs 35A conductors — that is 8 AWG on the 60°C column (10 AWG tops out at 30A) but 10 AWG exactly meets it on the 75°C column. When in doubt, use 60°C.
No — hermetic refrigerant motor-compressors follow NEC Article 440, not 430. Use the equipment nameplate MCA and MOP values, which already include the 125% factor. Applying Article 430 multipliers to HVAC equipment is a classic and dangerous mistake.