Superheat & Subcooling

Pressures in, diagnosis out.

Charging by "beer can cold" is how compressors die. The correct method reads pressures and line temperatures, converts them through the refrigerant's pressure-temperature relationship, and compares superheat and subcooling against the manufacturer target. This calculator does the PT conversion for R-410A and R-22, flags values outside field bands, and names the likely fault from the classic diagnosis matrix — undercharge, overcharge, or restriction.

Why people use this

HVAC techs use it on every service call — gauges and clamp thermometers in, charge verdict out, without flipping through a PT card. The diagnosis matrix catches the classic misread: high superheat with high subcooling is a restriction, not an undercharge, and adding refrigerant to it kills compressors.

How it works

  1. Pick the refrigerant and metering device — TXV systems charge by subcooling; fixed-orifice by superheat.
  2. Enter suction pressure and suction line temperature → superheat appears with its verdict.
  3. Enter liquid pressure and liquid line temperature → subcooling appears against the manufacturer target.
  4. Read the combined diagnosis: high superheat + low subcooling means undercharged; the reverse means overcharged.

Common questions

Which do I use to charge — superheat or subcooling?

It depends on the metering device. TXV systems hold superheat constant by design, so you charge to the manufacturer's subcooling spec (commonly 8–12°F). Fixed-orifice (piston) systems let superheat float with load, so you charge to a superheat target from the manufacturer chart based on indoor wet-bulb and outdoor dry-bulb temperatures.

What does high superheat with low subcooling mean?

The classic undercharge signature: not enough refrigerant mass, so the evaporator starves (high superheat) and the condenser cannot stack liquid (low subcooling). The reverse — low superheat with high subcooling — points to overcharge. High on both suggests a restriction or low evaporator airflow, not a charge problem.

How long should the system run before I read gauges?

Ten to fifteen minutes minimum at stable conditions — pressures drift while the coil pulls down. Reading early is the most common way techs misdiagnose charge. Also insulate your temperature clamps and wait for them to settle; a bad line-temp reading corrupts both numbers.

Can I top off R-410A like R-22?

Not ideally. R-410A is a near-azeotropic blend; significant leaks can shift its composition, so best practice is recover and recharge by weight. R-22 is a single-component refrigerant and tolerates topping off — though as a phased-out HCFC, it is expensive and reclaimed-only. Either way, refrigerant handling requires EPA Section 608 certification.