Voltage Drop Calculator

Will that 100-foot run actually deliver 120 volts?

Every long wire run loses voltage — to a shed, an RV pedestal, a well pump, a shop. Undersized wire means dim lights, hot conductors, and motors that die young. This calculator runs the standard NEC formula (Vd = 2 × K × L × I ÷ CM), checks the result against the 3% branch-circuit guideline, and tells you the smallest copper or aluminum gauge that passes.

Why people use this

Electricians sizing runs to outbuildings, DIYers wiring a shed, and RV owners spec-ing a pedestal all hit the same wall: the wire is legal by ampacity but drops too many volts over distance. This catches that before the trench is backfilled.

How it works

  1. Enter the load in amps and the one-way distance in feet.
  2. Pick system voltage, wire gauge, and copper or aluminum.
  3. Read the voltage drop in volts and percent, and the NEC 3% pass/fail.
  4. Use the "smallest size that passes" output to spec the right wire before you trench.

Common questions

How much voltage drop is acceptable?

The NEC recommends (as a performance guideline, not a mandate) no more than 3% on a branch circuit and 5% total for feeder plus branch. At 120 V, 3% is 3.6 volts. Sensitive electronics and motors care more than light bulbs.

What size wire for 20 amps at 100 feet?

12 AWG copper carries 20 A legally, but at 100 feet it drops 7.9 V (6.6%) — over the guideline. Even 10 AWG fails at 5.0 V (4.1%). You need 8 AWG (3.1 V, 2.6%) to pass. Distance, not just amps, is what upsizes wire — run the numbers before you buy.