Load amps in, wire gauge and breaker out.
Wire sizing has two rules that collide: the conductor must carry the load (ampacity), and continuous loads must be multiplied by 125% before sizing anything. This calculator applies both, using NEC Table 310.16 75°C ampacities for copper and aluminum, and outputs the minimum gauge and standard breaker size.
Anyone adding an EV charger, hot tub, or shop heater asks "what wire and what breaker?" — and the 125% continuous-load rule is exactly what casual answers miss. This applies the NEC table and the rule together, copper or aluminum.
Intermittent 50 A load: 8 AWG copper (50 A at 75°C). Continuous: 50 × 1.25 = 62.5 A design, so 6 AWG copper and a 70 A breaker. The continuous rule is why EV chargers upsize wire.
Yes for feeders and large branch circuits — it is roughly two gauges larger and much cheaper per foot. Use AL-rated terminals, antioxidant compound, and proper torque; the 1970s fire problems were termination failures, not the metal.