Calculators for Electricians & Electrical Contractors

Ampacity keeps it legal, voltage drop keeps it working — the difference shows up 100 feet from the panel. These are the NEC table calculations you already know, running at truck speed, plus the business math for when the job is yours.

The questions these tools answer

Common questions

Why does the voltage drop calculator matter if my wire meets ampacity?

Ampacity is about heat; voltage drop is about performance. A 12 AWG copper run is legal at 20 A but drops 7.9 volts over 100 feet — motors run hot, LEDs flicker, EV chargers fault out. NEC's 3% guideline upsizes wire on distance long before ampacity does.

What is the 125% continuous load rule?

NEC 210.19/215.2: loads running 3+ hours (EV chargers, heaters, lighting) must be multiplied by 1.25 before sizing wire and breaker. A 40 A EVSE needs wire and a breaker sized for 50 A — that is the rule everyone's cousin skips.

Can I trust these numbers for permitted work?

Use them for estimates, bids, and sanity checks — the tables are NEC Chapter 9 and 310.16 at 75°C. Final design belongs to the licensed electrician of record and the AHJ; terminals, bundling, and ambient temperature can all change legal ampacity.

Browse all 500+ free calculators →